Windmill Cables | |||
EPR/HFXLEVA LSOH 0.6/1kV Torsion Resistant Power Cable |
Windmill Cables
Indoor/Outdoor PROFIBUSApplication
These cables are used in the cell and field area, suitable for indoor or outdoor installation and are equipped with special PVC or PE sheath.
Standards
DIN 19245 T3
EN 50170
Construction
Conductor: Bare copper 1×22AWG.
Insulation: Foam skin PE.
Cable Element: Two cores with filler.
Screen 1: Polyester tape over stranded bundle.
Screen 2: Aluminium/Polyester tape.
Overall Screen: Tinned copper braid.
Sheath: PVC/PE.
Technical Data
Operating Temperatures |
-40℃~+70℃ |
Minimum Bending Radius |
120mm |
Impedance |
150Ohm +/-10% |
Maximum Conductor Resistance @20°C |
55Ohm/km |
Nominal Mutual Capacitance |
35nF/km |
Minimum Insulation Resistance |
1GOhm×km |
Attenuation @9.6kHz |
<2.5dB/km |
Attenuation @38.4kHz |
<4dB/km |
Attenuation @4kHz |
<22dB/km |
Attenuation @16kHz |
<42dB/km |
Flame Retardant |
IEC 60332-1/FT 1/FT 4 |
UV Resistant |
Yes |
Dimensions and Weight
Construction |
Nominal Overall Diameter |
Nominal Weight |
No. of cores×mm |
mm |
kg/km |
1×2×0.64 (PVC Sheath) |
8.0 |
75 |
1×2×0.64 (PE Sheath) |
8.0 |
65 |